METSEPM5110METSEPM5330METSEPM5560
PowerLogic PM5000 series
Technical datasheet
Basic multi-function meters
2
2013
Functions and characteristics
P B 11177
6
PowerLogic ™
PM5000 Series meter
PowerLogic ™ PM5100, PM5300 and PM5500 series
The PowerLogic ™ PM5000 power meter is the ideal fit for cost management
applications. It provides the measurement capabilities needed to allocate energy usage, perform tenant metering and s
ub-billing, pin-point energy savings, optimize equipment efficiency and utilization, and perform a high level assessment of the power quality of the electrical network.
In a single 96 x 96 mm unit, with a graphical display, all three phases, neutral and ground can be monitored simultaneously.
The bright, anti-glare display features large characters and powerful backlighting for easy reading even in extreme lighting conditions and viewing angles.
Easy to understand menus, text in 8 selectable languages, icons and graphics create a friendly environment to learn about your electrical network.Highly accurate devices with global billing certifications.Applications
Cost management: Cost saving opportunities becomes clear once you understand how and when your facility uses electricity. The PowerLogic ™ PM5000 series meters are ideal for:• Sub billing / tenant metering: allows a landlord, property management firm,
condominium association, homeowners association, or other multi-tenant property to bill tenants for individual measured utility (electricity) usage. MID approved meters for billing applications across Europe.• Cost allocation: allocate energy costs between different departments (HVAC,
indoor and outdoor lighting, refrigeration, etc), different parts of an industrial process or different cost centres. Cost allocation systems can help you save
money by making changes to your operation, better maintaining your equipment, taking advantage of pricing fluctuations, and managing your demand.Network management: Improving reliability of the electrical network is key for success in any business. Monitoring values such as voltage levels, harmonic distortion and voltage unbalance will help you to ensure proper operation and
maintenance of your electrical network and equipment. PowerLogic ™ PM5000 series meters are the perfect tool for:• Basic Power Quality monitoring: power quality phenomena can cause
undesirable effects such as heating in transformers, capacitors, motors,
generators and misoperation of electronic equipment and protection devices. • Min/ Max monitoring (with timestamp): understanding when electrical
parameters, such as voltage, current and power demand, reach maximum and minimum values will give you the insight to correctly maintain your electrical network and assure equipment will not be damaged.• Alarming: alarms help you to be aware of any abnormal behavior on the
electrical network in the moment it happens.• WAGES monitoring: take advantage of the input metering on PM5000 meters
to integrate measurements from 3rd party devices such as water, air, gas, electricity or steam, meters.Main characteristics Easy to install
Mounts using two clips, in standard cut out for DIN 96 x 96mm, no tools required. Compact meter with 72mm (77mm for PM5500) depth connectable up to 690 VL-L without voltage transformers for installations compliant with category III.
Easy to operate
Intuitive navigation with self-guided, language selectable menus, six lines, four concurrent values. Two LEDs on the meter face help the user confirm normal
operation with a green LED - heartbeat/communications indicator, and the amber LED - customizable either for alarms or energy pulse outputs.
Easy circuit breaker monitoring and control
The PM5300 provides two relay outputs (high performance Form A type) with capability to command most of the circuit
breaker coils directly. For Digital Inputs, monitored switches can be wired directly to the meter without external power supply.PM5500 series have 4 status inputs (digital) and 2 digital output (solid state) to use for WAGES monitoring, control and alarm annunciation.
Accurate energy measurement for precise cost allocation:
3
2013
Functions and characteristics (cont.)
Direct metering of neutral current
The PM5500 has a fourth CT for measuring neutral current. In demanding IT
applications, where loads are non-linear (i.e. switching power supplies on computers/servers), measuring neutral curren
t is essential to avoid overload and resulting outage. In addition, the PM5500 provides a calculated ground current value, not available in meters with 3 CTs.
欧美无mate30pro巨Power Quality analysis
The PM5000 offers Total Harmonic Distortion (THD/thd), Total Demand
Distortion (TDD) measurements and individual harmonics (odd) magnitudes and angles for voltage and current:
These types of power quality parameters help to identify the source of harmonics that can harm transformers, capacitors, generators, motors and electronic equipment.
Load management
Peak demands with time stamping are provided. Predicted demand values can be used in combination with alarms for basic load shedding applications.
Alarming with time stamping
A different combination of set point driven alarms and digital alarms with 1s time stamping are available in the PM5000 family:
Alarms can be visualized as Active (the ones that have picked up and did not drop out yet) or Historical (the ones that happened in the past).
Alarms can be programmed and combined to trigger digital outputs and mechanical relays (PM5300).
The PM5000 series keeps an alarm log with the active and historical alarms with date and time stamping.
Load timer
A load timer can be set to count load running hours based on a minimum current withdraw, adjustable to monitor and advise maintenance requirements on the load.High Performance and accuracy
IEC 61557-12 Performance measuring and monitoring devices (PMD)
Defines the performance expectation based on classes. It defines the allowable
error in the class for real and reactive power and energy, frequency, current, voltage, power factor, voltage unbalance, voltage and current harmonics (odds), voltage
THD, current THD, as well as ratings for temperature, relative humidity, altitude, start-up current and safety. It makes compliant meters readings comparable - they will measure the same values when connected to the same load.
Meets IEC 61557-12* PMD/[SD|SS]/K70/0.5 for PM5100 and PM5300Meets IEC 61557-12* PMD/[SD|SS]/K70/0.2 for PM5500
Legal billing compliance
MID compliance is compulsory for billing applications across Europe.
In addition to billing applications, for facility managers responsible for energy cost MID means same level of quality as a billing meter.MID ready compliance, EN50470-1/3 – Class C *Pending approval.
P B 111768
P B 111770
P B 111768
PowerLogic ™ PM5500 meter
PowerLogic ™ PM5300 meter
PowerLogic ™ PM5100 meter
Basic multi-function metering PM5000 Series
Functions and characteristics (cont.)
42013
发布评论