李辉1汤小亮*2邹松1陈焰华2金碧辉2邱雅凡2
1武汉市建筑节能办公室2中信建筑设计研究总院有限公司
设计人员关注,相关规范也均规定了空调供冷供热水系统的耗电输冷热比计算方法及限值。本文结合工程实例,分析了规范计算方法在区域供冷供热系统耗电输冷热比计算中适应性和存在的问题,探讨了规范中计算方法的调整完善之处。
关键词:区域供冷供热耗电输冷热比水泵效率
Analysis and Discussion on the Calculation of
EC(H)R in District Power Supply System
LI hui 1,TANG Xiao-liang*2,ZOU Song 1,CHEN Yan-hua 2,JIN Bi-hui 2,QIU Ya-fan 2
1Wuhan Building Energy Conservation Office
2CITIC General Institute of Architectural Design and Research Co.,Ltd.
Abstract:With the increasing scale of civil buildings,the transmission and distribution system of cooling and heating system is more and more complex,and the energy consumption is higher and higher.The energy-saving design has attracted the attention of designers,relevant standard also given the calculation method and limit value of EC(H)R.Based on an engineering example,this paper analyzes the adaptability and existing problems of the standard calculation method in the calculation of EC(H)R in the district cooling and heating system,and discusses the adjustment and improvement of the calculation method in the standard.
Keywords:district cooling and heating,EC(H)R,pump efficiency
收稿日期:2019-7-15
通讯作者:汤小亮(1983~),男,硕士,高工;武汉市江岸区四唯路8号(430014);E-mail:*****************
0引言
近年来,随着我国城镇化的快速发展,单个项目
达到五十万平方米乃至一百多万平方米的建筑不断涌现,为了实现区域能源的高效集约利用,区域供冷供热系统在工程项目中得到了越来越多的应用,大型的供冷供热系统不仅使得空调水管网和输送动力系统变得更复杂,空调冷热水输送系统的能耗也变得越高。据相关项目测试研究,
办公大楼的空调水系统能耗占到了空调总能耗的25%以上[1]。可见,
如何合理设计一个大型区域空调水系统,并准确计算其耗电输冷热比,使其满足相应设计标准和规范的要求显得尤为重要。
本文结合武汉某示范基地项目的暖通空调设计
实例及《公共建筑节能设计标准》(GB 50189-2015)[2]空调耗电量计算
和
《民用建筑供暖通风与空气调节设计规范》
(GB 50736-2012)[3]
中有关空调水系统的耗电输冷热比计算
方法,研究和分析该计算方法在区域供冷供热空调水系统中存在的疑点和难点,
并探讨计算方法的可改进和优化之处,以供类似区域供冷供热系统在空调水系
第39卷第7期2020年7月
建筑热能通风空调
Building Energy &Environment Vol.39No.7Jul.2020.60~62
文章编号:1003-0344(2020)7-060-4